In accordance with | IEC61643-1:2011;UL1449 3rd | |
---|---|---|
Category IEC | I+II/B+C | |
Operating voltage Un | AC | 110V |
Max. Continuous operating voltage Uc | L-N (AC) | 175V |
N-PE (AC) | 150V | |
Nominal discharge current (8/20us) In | L-N | 20KA |
N-PE | 20KA | |
Max. discharge current (8/20us) Imax | L-N | 50KA |
N-PE | 50KA | |
Voltage protection level Up | L-N@In | 0.8KV |
L-N@6KV/3KA | 0.6KV | |
N-PE(1.2/50μs) | 0.8KV | |
Response time | L-N | ≦25ns |
N-PE | ≦100ns | |
Follow current | L-N | No |
N-PE | 100Arms @Uc | |
Operating temperature range | -40℃~+80℃ | |
Cross-section of connection wire | Single-strand: 35mm²(AWG: 4~1); multi-strand: 25mm²(AWG: 4~1) | |
Mounting | 35mm DIN-rail in accordance with EN 50022/DIN46277-3 | |
Enclosure material | Thermoplastic; Extinguishing degree: UL94 V-0 | |
Degree of protection | IP20 | |
Failure indication | green: normal; Red : failure ( Thermal disconnect) | |
Remote monitoring contact (optional) | Relay output, NO/NC AC:250V/0.5A ; DC:250V/0.1A ; DC:125V/0.2A ; DC:75V/0.5A | |
Cross-section of connection wire | Max. 1.5mm² (AWG: 16~15) | |
Dimension (mm) | 98(L)*36(W)*66(H) |