Model No | AVC-110 |
---|---|
Measuring method | Chemical-electro |
Response time | τ90 ≦ 30 秒 |
Accuracy (at 25℃) | ±5% for 0~100ppm ; ±10% for 100~250ppm |
Repeatability | Reading ± 2 % |
Zero drift | ≦5% / yr. |
Measuring range | 0~100ppm ; 0~250ppm |
Signal output | DC 4 ~ 20mA/ DC 0 ~ 10 V/RS-485 (Modbus RTU) |
Alarm output | Relay output N.O,N.C ( 2A / 30V DC) ; Relay setting 50 ppm |
Linearity error | <10 ppm ( at -10℃~ 50 ℃) |
Calibration interval (recommended) | 12 months |
Pressure range | 1 atm ± 10 % |
Environmental | -10℃ ~ 50℃ ; 15 ~ 90%RH |
Transportation & storage | -10℃~ 50℃ |
Warm-up time | ≤ 1.5 min. ( Full scale,≤ 15 minutes) |
Power supply | 12 ~ 36V AC/DC,50/60Hz |
Installation | Wall-mount |
Dimensions (mm) | 113.57(H) x 80(W) x 28.79(D) |
Case material | ABS |
Protection rate | IP30 |
*All information is subject to change without prior notice. |