AQD-100
Air Quality Display
For CO2, Temperature and humidity measurements
AQD series displays three most crucial parameters of IAQ; CO2 level, humidity and temperature. It also provides date, day and time. 
It uses good quality sensors; such as the NDIR CO2 sensor, temperature and humidity sensors which are usually available only in laboratory air quality diagnostic equipment. 
AQD series measures CO2 concentration which may not be noticeable by us and used the reading to control ventilation 
so that the indoor CO2 level can be kept below the recommended ASHRAE limit of 1000ppm. 
Monitoring humidity is very important as extended period in an area with humidity over 60% or below 40% can create conditions for mold and mildew growth that may cause allergies and affect general health.
 
General
TypeWall mount
ParametersCO2, Relative Humidity, Temperature
Operating Environment-10 ~ 60 ℃ / 0 ~ 95%RH, non-condensing
Storage temperature-10~60 ℃
ClockReal time clock with battery backup
Power supply12 VDC (supply with an AC adapter 100~240V / 50~60Hz )
Current consumption1.2A (max)
Display7 segment LED display
Memory capacity60000 values
CO2 Measurement
Measurement principleNon-dispersive infrared (NDIR) with automatic calibration
Measurement range0~9999 ppm
Accuracy tolerance0~2000ppm ± 3% and ± 40 ppm note1 and 2
Response time2 minutes by 90%
MaintenanceMaintenance-free for normal indoor applications
Environmental-10 ~ 60 ℃/ 0 ~ 95%RH, non-condensation
Display digit4 digits, 0 ~ 9999
Relay setting1200ppm
Hysteresis100ppm
Humidity Measurement
Measurement range0 ~ 95 %RH
Accuracy tolerance± 3 %RH (typical)
Repeatability± 0.1 %RH
Response time τ63< 8 s (τ63%, 25℃)
Long-term drift< 0.5 %RH / year
Display digit2 digits, 0 ~ 99
Relay setting70%RH
Hysteresis5%RH
Temperature Measurement
Measurement range-10 ~ 60 ℃
Accuracy tolerance± 0.3 ℃ (typical)
Repeatability± 0.1 ℃
Response time τ635 ~ 30 s (τ63%, 25℃)
Long-term drift< 0.04 ℃/ year
Display digit3 digits (One decimal point), 0.0 ~ 99.9
Relay setting28℃
Hysteresis1℃
Outputs
RS-485RS485 (Modbus RTU)
Relay3 Relay outputs for CO2, relative humidity, and temperature respectively.
N.O. and N.C. (2A/30VDC)
Mechanical
Housing materialPMMA panel (4mm), SPCC casing (1mm)
Dimensions527 x 217 x 32 mm
Weight2600g
Note 1: In normal IAQ applications. Accuracy is defined after minimum 3 weeks of continuous operation with ABC. However, some industrial
applications do require maintenance.℃
Note 2: Accuracy is specified at room temperature +25°C and at normal pressure 101.3 kPa. Specification is referenced to certified calibration
mixtures. Uncertainty of calibration gas mixtures (+-1% currently) is to be added to the specified accuracy for absolute measurements.